Can I change and connect a car lead acid battery of 12 volt 43 ah to a computer UPS?
My UPS has inbuilt battery of 12 volt 7ah to get longer backup of time, by changing the battery of higher ampere there will be any possibility of damage on the ups or what ?
Tags: Ranjan
0
Ranjan 21 april 2012 , 21:50

Comments

0 Siera April 22, 2012, 16:22
Ranjan, yes you can. There won't be any damage to you UPS. But check your UPS battery does it has REALLY 12v inbuilt battery. Everything that can damage your UPS is other voltage and not ah.
0 BeatFreak June 21, 2012, 13:34
I know this is a late reply, but as long as the battery is the correct Voltage you can change the Amp Hours to what you require and no damage would occur. The only thing you need to remember is the UPS will be limited to how many ah the UPS itself can recharge . For example if the UPS is fitted with 7ah and you change this to 100ah, then the battery will probably never recharge after a full discharge.

I hope this helps.